MODBUS 4 CHANNEL ANALOGUE I/P,O/P MODULE

Categories: ,

Description

Introduction:
This Rs485 Analogue module is used through Modbus communication protocol, in this instrument user can do calibration of four channels and read and write Modbus ID this can be done through Modbus, this instrument easy to use with PLC/DC. It has 4 nos 0-10vDc/4-20mA output optical and Galvani isolated and user can be using every channel via standard Modbus protocol. And it has 4 nos Analogue input like AC/DC V /4-20mA DC. Its operating power supply voltage is 24vdc.
Modbus communication protocol:
1. Baud Rate: 9600 B/S
2. Data Bits :8
3. Party: None
4. Stop Bit: One
5. Communication Mode: RTU 8 Bit

ADDRESS
SN. ADDRSS PARAMETER REMARK
01 4001 IPNUT CHANNEL1 2 BYTE DATA
02 4002 INPUT CHANNEL 2 2BYTE DATA
03 4003 INPUT CHANNEL 3 2BYTE DATA
04 4004 INPUT CHANNEL 4 2 BYTE DATA
05 5001 OUTPUT CHANNEL 1 0-4000 VALUE
AS TO BE WRITE TO DAC
= 0-10VDC/0-20mA O/P
06 5002 OUTPUT CHANNEL 2 0-4000 VALUE
AS TO BE WRITE TO DAC
= 0-10VDC/0-20mA O/P
07 5003 OUTPUT CHANNEL 3 0-4000 VALUE
AS TO BE WRITE TO DAC
= 0-10VDC/0-20mA O/P
08 5004 OUTPUT CHANNEL 4 0-4000 VALUE
AS TO BE WRITE TO DAC
= 0-10VDC/0-20mA O/P
09 6001 Chan1 AI1 CURRENT VALUE(10BIT) AI1 CURRENT VALUE 0-1024(MAX) at 38vAC/0-20mA(Max)
10 6002 Chan2 AI2 CURRENT VALUE(10BIT) AI2 CURRENT VALUE 0-1024(MAX) at
38vAC/0-20mA(Max)
11 6003 Chan3 AI3 CURRENT VALUE(10BIT) AI3 CURRENT VALUE 0-1024(MAX)at
38vAC/0-20mA(Max)
12 6004 Chan4 AI4 CURRENT VALUE(10BIT) AI4 CURRENT VALUE 0-1024(MAX)at
38vAC/0-20mA(Max)